SANS Standard 6.35/11kV-XLPE Insulated Middle Voltage(MV) Power Cable
Application
Copper or Aluminium Conductors, single or 3 Core, Armoured or Unarmoured, bedded and served in PVC or non-halogenated material,Rated Voltage 6,6 up to 33kV, made to SANS or other National or International Standards.
Construction
1 Core or 3 Core, circular Aluminium or Copper stranded conductor, XLPE/PE insulated, Individually copper tape screened, Flame retardant / low halogen flame retardant PVC sheathed.
Cable Identification
FRPVC (red stripe), LHFRPVC (blue stripe), HFFR (white stripe), PE (no stripe).
Characteristics
Voltage Rating: 6350/11000V –SANS1339
Temperature limits: -15°C to +90°C
Should not be installed at temperatures below 0°C or above +60°C
Data Sheet
6.35/11(12)kV 1CORE AL/XLPE/PVC/AWA/PVC AND CU/XLPE/PVC/AWA/PVC Type A
Conductor size |
mm² |
50 |
70 |
95 |
120 |
150 | 185 |
240 |
300 |
400 |
500 |
630 |
Conductor diameter |
mm |
8.35 |
10.05 |
11.90 |
13.25 |
14.70 | 16.23 |
18.46 |
20.75 |
24.05 |
27.42 |
30.45 |
Insulation diameter |
mm |
17.02 |
18.72 |
20.57 |
21.92 |
23.37 | 24.90 |
27.13 |
29.42 |
33.52 |
37.67 |
40.70 |
Bedding diameter |
mm |
21.87 |
23.57 |
25.42 |
26.77 |
28.22 | 29.75 |
31.98 |
34.27 |
38.37 |
42.73 |
45.96 |
Armour diameter |
mm |
25.07 |
26.77 |
28.62 |
29.97 |
32.22 | 33.75 |
35.98 |
38.27 |
42.37 |
47.73 |
50.96 |
Cable diameter |
mm |
29.54 |
31.45 |
33.30 |
34.85 |
37.31 | 38.84 |
41.27 |
43.56 |
48.07 |
53.63 |
57.07 |
Cable mass (approximate) |
kg/m |
1.353 |
1.634 |
1.955 |
2.258 |
2.692 | 3.096 |
3.743 |
4.417 |
5.527 |
6.936 |
8.481 |
DC Resistance at 20°C |
Ω/km |
0.387 |
0.268 |
0.193 |
0.153 |
0.124 | 0.099 |
0.075 |
0.060 |
0.047 |
0.037 |
0.028 |
AC Resistance at 90°C |
Ω/km |
0.494 |
0.342 |
0.247 |
0.196 |
0.159 | 0.128 |
0.098 |
0.080 |
0.064 |
0.052 |
0.042 |
6.35/11(12)kV 1CORE AL/XLPE/UNARMORED/PVC AND CU/XLPE/UNARMORED/PVC Type B
Conductor size |
mm² |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
Conductor diameter |
mm |
8.50 |
10.00 |
12.00 |
13.50 |
15.00 |
16.50 |
19.00 |
21.50 |
24.00 |
27.50 |
31.50 |
Insulation diameter |
mm |
17.00 |
18.50 |
20.50 |
22.00 |
23.50 |
25.00 |
27.50 |
30.00 |
34.00 |
38.00 |
42.00 |
Cable diameter |
mm |
24.00 |
25.00 |
27.00 |
29.00 |
30.00 |
32.00 |
35.00 |
37.00 |
41.00 |
45.00 |
50.00 |
Cable mass (approximate) |
kg/m |
0.89 |
1.28 |
1.58 |
1.86 |
2.18 |
2.56 |
3.18 |
3.71 |
4.71 |
5.84 |
7.28 |
DC Resistance at 20°C |
Ω/km |
0.387 |
0.268 |
0.193 |
0.153 |
0.124 |
0.099 |
0.075 |
0.060 |
0.047 |
0.037 |
0.028 |
AC Resistance at 90°C |
Ω/km |
0.494 |
0.342 |
0.247 |
0.196 |
0.159 |
0.128 |
0.098 |
0.080 |
0.064 |
0.052 |
0.042 |
6.35/11(12)kV 3CORE AL/XLPE/PVC/SWA/PVC AND CU/XLPE/PVC/SWA/PVC Type A
Conductor size |
mm² |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
Conductor diameter |
mm |
4.8 |
6.0 |
7.2 |
8.4 |
9.9 |
11.7 |
13.4 |
14.6 |
16.4 |
18.8 |
20.4 |
24.3 |
Insulation diameter |
mm |
13.5 |
14.7 |
15.9 |
17.1 |
18.6 |
20.4 |
22.1 |
23.3 |
25.1 |
27.5 |
29.1 |
33.8 |
Bedding diameter |
mm |
36.6 |
39.4 |
42.0 |
44.8 |
48.0 |
52.1 |
56.0 |
58.6 |
62.6 |
68.0 |
71.7 |
82.1 |
Armour diameter |
mm |
40.6 |
44.4 |
47.0 |
49.8 |
53.0 |
57.1 |
61.0 |
64.9 |
68.9 |
74.3 |
78.0 |
88.4 |
Cable diameter |
mm |
45.3 |
49.3 |
52.1 |
55.1 |
58.5 |
62.8 |
67.1 |
71.2 |
75.5 |
81.3 |
85.4 |
96.1 |
Cable mass (approximate) |
kg/m |
3.67 |
4.51 |
5.02 |
5.67 |
6.65 |
7.88 |
8.95 |
11.0 |
12.47 |
14.76 |
17.23 |
21.36 |
DC Resistance at 20°C |
Ω/km |
1.150 |
0.727 |
0.524 |
0.387 |
0.268 |
0.193 |
0.153 |
0.124 |
0.099 |
0.075 |
0.060 |
0.047 |
AC Resistance at 90°C |
Ω/km |
1.466 |
0.927 |
0.668 |
0.494 |
0.342 |
0.247 |
0.196 |
0.159 |
0.128 |
0.099 |
0.080 |
0.064 |
6.35/11(12)kV 3CORE AL/XLPE/UNARMORED/PVC AND CU/XLPE/UNARMORED/PVC Type B
Conductor size |
mm² |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
Conductor diameter |
mm |
4.8 |
6.0 |
7.2 |
8.4 |
9.9 |
11.7 |
13.4 |
14.6 |
16.4 |
18.8 |
20.4 |
20.4 |
Insulation diameter |
mm |
13.5 |
14.7 |
15.9 |
17.1 |
18.6 |
20.4 |
22.1 |
23.3 |
25.1 |
27.5 |
29.1 |
29.1 |
Bedding diameter |
mm |
34.5 |
37.1 |
39.7 |
42.3 |
45.6 |
49.0 |
52.7 |
55.3 |
59.2 |
64.3 |
67.8 |
67.8 |
Cable diameter |
mm |
39.1 |
41.6 |
44.4 |
47.2 |
50.7 |
54.5 |
58.4 |
61.2 |
65.3 |
70.7 |
74.6 |
74.6 |
Cable mass (approximate) |
kg/m |
1.74 |
2.133 |
2.61 |
3.11 |
3.86 |
4.60 |
5.43 |
6.43 |
7.61 |
9.46 |
11.50 |
14.16 |
DC Resistance at 20°C |
Ω/km |
1.150 |
0.727 |
0.524 |
0.387 |
0.268 |
0.193 |
0.153 |
0.124 |
0.099 |
0.075 |
0.060 |
0.047 |
AC Resistance at 90°C |
Ω/km |
1.466 |
0.927 |
0.668 |
0.494 |
0.342 |
0.247 |
0.196 |
0.159 |
0.128 |
0.099 |
0.080 |
0.064 |