IEC/BS Standard PVC Insulated LV Power Cable

With the characteristics of stable capability, advanced technology, comprehensive material sources, low price, strong adaptability to the environment, good flexibility and easy to be laid and maintained, the PVC insulated power cables are used in fixed laying on transmission and distribution electrical lines with A. C. 50Hz and rated voltage up to 6kV.

    Application

    PVC Insulated Cable is used as power distribution and transmission line at rated voltage 0.6/1KV.

    Like power networks, underground, outdoor and indoor applications and within cable ducting.

    Construction

    Conductor: Class 2 stranded copper conductor or aluminium conductor

    ETP0E3Nykl

    Number of cable cores:one core(sing core),two cores(double cores),three cores, four cores (four equal-section-area cores of three equal-section-area and one smaller section area neutral core),five cores (five equal-section-area cores or three equal-section-area cores and two small area neutral cores).

    Insulation: Polyvinyl chloride (PVC).

    Armour method: Unarmored or Steel Wire Armour (SWA), Steel Tape Armour (STA), Aluminium Wire Armour (AWA), Aluminium Tape Armour (ATA).

    Sheath: Polyvinyl chloride PVC.

    Performance characteristics

    1. The long-term permissible operation temperature of conductor shall not be higher than 70℃.2. Conductor maximum short circuit(not more than 5 seconds)temperature shall not be higher than 160℃.3. The cables is not limited by drop in level when being laid,and the environment temperature shall not be 0℃.4. Perfect chemical stability,resistant against acids, alkalis,grease and organic solvents,and flame retardance.5. Light weight, perfect bending properties, installed and maintained easily and conveniently.6. Voltage rating: 600/1000 Volts7. Temperature rating: Fixed -25°C to +90°C

    Standards

    BS 6346IEC/EN 60502-1, IEC/EN 60228Flame Retardant according to IEC/EN 60332-1-2

    Data Sheet

    600 /1000 V – Two core copper conductor pvc insulated steel wire armoured pvc sheathed cables(CU / PVC / PVC / SWA / PVC)

    Nominal area of conductor Maximum conductor resistance at 20°c Thickness of insulation Thickness of  extruded bedding Armour wire diameter Thickness of outer sheath Approx.overall diameter Approx.cable weight
    mm2 Ohm/km mm mm mm mm mm kg/km
    1.5* 12.1 0.7 0.8 0.9 1.3 12.6 305
    1.5 12.1 0.7 0.8 0.9 1.4 13.2 310
    2.5* 7.41 0.8 0.8 0.9 1.4 14 370
    2.5 7.41 0.8 0.8 0.9 1.4 14.4 390
    4 4.61 0.8 0.8 0.9 1.4 15.4 460
    6 3.08 0.8 0.8 0.9 1.5 16.8 550
    10 1.83 1 0.8 1.25 1.6 19.9 835
    16 1.15 1 0.8 1.25 1.6 22.1 1050
    25** 0.727 1.2 1 1.6 1.7 26.8 1610
    35** 0.524 1.2 1 1.6 1.8 29.2 1950
    50** 0.387 1.4 1 1.6 1.9 32.7 2230
    70** 0.268 1.4 1 1.6 1.9 35.9 2790
    95** 0.193 1.6 1.2 2 2.1 42.1 3710
    120** 0.153 1.6 1.2 2 2.2 45.3 4580
    150** 0.124 1.8 1.2 2 2.3 49.1 5410
    185** 0.0991 2 1.4 2.5 2.4 54.4 6890
    240** 0.0754 2.2 1.4 2.5 2.5 60.7 8430
    300** 0.0601 2.4 1.6 2.5 2.7 66.3 10140
    400** 0.047 2.6 1.6 3.15 2.9 73.3 12500

    * Circular solid conductors (Class 1).All other conductors Circular stranded or circular stranded compacted (Class 2).All the cables are Insulated with either PVC Type 5 Heat Resisting 85℃ compound and sheathed with PVC.Type 9/ ST2 compound Or PVC Type A/TIl compound and sheathed with PVC Type ST1/TM1 compound.Cables conform to BS 6346.* * cables with sector shaped conductors having lesser overall dimensions, weight and cost are available on request.

    600 / 1000 V – Three core copper conductor pvc insulated steel wire armoured pvc sheathed cables(CU/PVC/PVC/SWA/PVC and CU/PVC/SWA/PVC)

    Nominal area of conductor Maximum conductor resistance at 20°c Thickness of insulation Thickness of bedding Dia. Of armour wire Thickness of outer sheath Approx.overall diameter Approx.cable weight
    Extruded bedding Lapped bedding Extruded bedding Lapped bedding Extruded bedding Lapped bedding
    mm2 Ohm/km mm mm mm mm mm kg/km
    1.5* 12.1 0.7 0.8 0.9 1.4 13.3 340
    1.5 12.1 0.7 0.8 0.9 1.4 13.7 355
    2.5* 7.41 0.8 0.8 0.9 1.4 14.6 415
    2.5 7.41 0.8 0.8   0.9 1.4 15 435
    4 4.61 0.8 0.8 0.9 1.4 16.1 515
    6 3.08 0.8 0.8 1.25 1.5 18.3 720
    10 1.83 1 0.8 1.25 1.6 20.9 960
    16 1.15 1 0.8 1.25 1.6 23.2 1240
    25 0.727 1.2 1 0.8 1.6 1.7 25.6 24.5 1670 1550
    35 0.524 1.2 1 0.8 1.6 1.8 28.1 27 2050 1920
    50 0.387 1.4 1 0.8 1.6 1.9 31.9 30.8 2610 2460
    70 0.268 1.4 1.2 0.8 2 2 35.5 34 3570 3360
    95 0.193 1.6 1.2 0.8 2 2.1 40.3 38.8 4590 4360
    120 0.153 1.6 1.2 0.8 2 2.2 43.5 42 5480 5230
    150 0.124 1.8 1.4 0.8 2.5 2.4 47.8 45.9 6940 6600
    185 0.0991 2 1.4 0.8 2.5 2.5 52.3 50.4 8270 7900
    240 0.0754 2.2 1.6 0.8 2.5 2.6 59 56.7 10330 9870
    300 0.0601 2.4 1.6 0.8 2.5 2.8 63.7 61.4 12480 11950
    400 0.047 2.6 1.6 0.8 2.5 3 71.1 68.8 15560 14970
    500 0.0366 2.8 1.8 0.8 3.15 3.6 78.8 76.1 19910 19130

    * Circular solid conductors (Class 1).Conductors including 16sqmm circular stranded (Class 2).25sqmm and above shaped stranded conductors(Class 2).All the cables are insulated with either PVC Type 5 Heat Resisting 85℃ compound and sheathed with PVC.Type 9/ST2 compound Or PVC Type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound.Drum size given above are for cables with extruded bedding.Cables up to 400sqmm conform to BS6346. 500sqmm cable conforms to IEC 60502-1.

    600 / 1000 V – Four core with reduced neutral copper conductor pvc insulated steel wire armoured pvc sheathed cables(CU/PVC/PVC/SWA/PVC and CU/PVC/SWA/PVC)

    Nominal area of conductor Maximum conductor resistance at 20°c Thickness of insulation Thickness of bedding Dia. Of armour wire Thickness of outer sheath Approx.overall diameter Approx.cable weight
    Phase Neutral Phase Neutral Phase Neutral Extruded Lapped Extruded bedding Lapped bedding Extruded bedding Lapped bedding
    mm2 Ohm/km mm mm mm mm mm kg/km
    10 * 6 1.83 3.08 1 1 1 1.25 1.8 22.7 1080
    16* 10 1.15 1.83 1 1 1 1.6 1.8 25.9 1530
    25 16 0.727 1.15 1.2 1 1 0.8 1.6 1.8 27.9 26.8 1930 1835
    35 16 0.524 1.15 1.2 1 1 0.8 1.6 1.9 31.5 30.4 2380 2270
    50 25 0.387 0.727 1.4 1.2 1 0.8 2 2 35.9 34.8 3250 3120
    70 35 0.268 0.524 1.4 1.2 1.2 0.8 2 2.1 39.4 37.9 4150 3945
    95 50 0.193 0.387 1.6 1.4 1.2 0.8 2 2.3 44.8 43.3 5360 5125
    120 70 0.153 0.268 1.6 1.4 1.4 0.8 2.5 2.5 49.3 47.4 6890 6575
    150 70 0.124 0.268 1.8 1.4 1.4 0.8 2.5 2.6 54 51.2 8110 7665
    185 95 0.0991 0.193 2 1.6 1.4 0.8 2.5 2.7 58.7 56.5 9730 9305
    240 120 0.0754 0.153 2.2 1.6 1.6 0.8 2.5 2.9 64.9 62.1 12030 11535
    300 150 0.0601 0.124 2.4 1.8 1.6 0.8 2.5 3.1 70.2 67.9 14660 13990
    300 185 0.0601 0.0991 2.4 2 1.6 0.8 2.5 3.2 70.4 68.1 14870 14350
    400 185 0.047 0.0991 2.6 2 1.8 0.8 3.15 3.4 80.2 76.6 19090 18125
    500 240 0.0366 0.0754 2.8 2.2 1.8 0.8 3.15 3.7 88.4 85.7 23300 22360

    * Phase conductors upto 16sqmm circular stranded(Class 2).Phase conductors 25sqmm and above shaped stranded (Class 2).All neutral conductors circular stranded (class 2).All the cables are insulated with either PVC Type 5 Heat Resisting 85℃ compound and sheathed with PVC.Type 9/ST2 compound Or PVC Type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound.Drum size given above are for cables with extruded bedding.* Cables conform to IEC 60502-1.

    600 / 1000 V – Four core copper conductor pvc insulated steel wire armoured pvc sheathed cables(CU/PVC/PVC/SWA/PVC and CU/PVC/SWA/PVC)

    Nominal area of conductor Maximum conductor resistance at 20°c Thickness of insulation Thickness of bedding Dia. Of armour wire Thickness of outer sheath Approx.overall diameter Approx.cable weight
    Extruded bedding Lapped bedding Extruded bedding Lapped bedding Extruded bedding Lapped bedding
    mm2 Ohm/km mm mm mm mm mm kg/km
    1.5* 12.1 0.7 0.8 0.9 1.4 14.1 385
    1.5 12.1 0.7 0.8 0.9 1.4 14.5 400
    2.5* 7.41 0.8 0.8 0.9 1.4 15.5 470
    2.5 7.41 0.8 0.8   0.9 1.4 16 495
    4 4.61 0.8 0.8 1.25 1.5 18.1 700
    6 3.08 0.8 0.8 1.25 1.5 19.6 8300
    10 1.83 1 0.8 1.25 1.6 22.4 1130
    16 1.15 1 1 1.6 1.7 26.4 1650
    25 0.727 1.2 1 0.8 1.6 1.8 27.9 26.8 2040 1890
    35 0.524 1.2 1 0.8 1.6 1.9 31.5 30.4 2550 2400
    50 0.387 1.4 1.2 0.8 2 2 36.3 34.8 3510 3300
    70 0.268 1.4 1.2 0.8 2 2.1 39.4 37.9 4450 4220
    95 0.193 1.6 1.2 0.8 2 2.2 44.6 43.1 5770 5510
    120 0.153 1.6 1.4 0.8 2.5 2.4 49.1 47.2 7350 6970
    150 0.124 1.8 1.4 0.8 2.5 2.5 53.5 51.6 8760 8390
    185 0.0991 2 1.4 0.8 2.5 2.6 58.6 56.3 10530 10040
    240 0.0754 2.2 1.6 0.8 2.5 2.8 64.2 61.9 13050 12520
    300 0.0601 2.4 1.6 0.8 2.5 3 70 67.7 15880 15300
    400 0.047 2.6 1.8 0.8 3.15 3.3 79.1 76.4 20710 20000
    500 0.0366 2.8 1.8 0.8 3.15 3.9 88.8 86.1 25400 24720

    * Circular solid conductors (Class 1).Conductors including 16sqmm circular stranded (Class 2).25sqmm and above shaped stranded conductors(Class 2).All the cables are insulated with either PVC Type 5 Heat Resisting 85℃ compound and sheathed with PVC.Type 9/ST2 compound Or PVC Type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound.Drum size given above are for cables with extruded bedding.Cables up to 400sqmm conform to BS6346. 500sqmm cable conforms to IEC 60502-1.

    600 / 1000 V – Five core copper conductor pvc insulated steel wire armoured pvc sheathed cables(CU/PVC/PVC/SWA/PVC and CU/PVC/SWA/PVC)

    Nominal area of conductor Maximum conductor resistance at 20°c Thickness of insulation Thickness of bedding Dia. Of armour wire Thickness of outer sheath Approx.overall diameter Approx.cable weight
    Extruded bedding Lapped bedding Extruded bedding Lapped bedding Extruded bedding
    mm2 Ohm/km mm mm mm mm mm kg/km
    1.5 12.1 0.7 0.8 1.25 1.8 18 601
    2.5 7.41 0.8 0.8 1.25 1.8 19.2 707
    4 4.61 0.8 0.8 1.25 1.8 21.8 915
    6 3.08 0.8 0.8 1.6 1.8 24 1197
    10 1.83 1 0.8 1.6 1.8 26.5 1517
    16 1.15 1 1 1.6 1.9 29.5 1948
    25 0.727 1.2 1 0.8 1.6 2 33.4 29.4 2605
    35 0.524 1.2 1 0.8 2 2.1 34.8 30.62 3283
    50 0.387 1.4 1.2 0.8 2 2.2 39 34.62 4183
    70 0.268 1.4 1.2 0.8 2 2.3 43.1 38.52 5394
    95 0.193 1.6 1.2 0.8 2.5 2.6 50.1 44.92 7487
    120 0.153 1.6 1.4 0.8 2.5 2.7 54.1 48.72 8935
    150 0.124 1.8 1.4 0.8 2.5 2.9 59.1 53.32 10711
    185 0.0991 2 1.4 0.8 2.5 3.1 64.9 58.72 12988
    240 0.0754 2.2 1.6 0.8 2.5 3.3 72.2 65.62 16369
    300 0.0601 2.4 1.6 0.8 3.15 3.6 80.7 73.52 20850
    400 0.047 2.6 1.8 0.8 3.15 3.8 88.92 81.32 25630
    500 0.0366 2.8 1.8 0.8 2.5 2.5 46.8 41.8 19916

    * Circular solid conductors (Class 1).Conductors including 16sqmm circular stranded (Class 2).25sqmm and above shaped stranded conductors(Class 2).All the cables are insulated with either PVC Type 5 Heat Resisting 85℃ compound and sheathed with PVC.Type 9/ST2 compound Or PVC Type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound.Drum size given above are for cables with extruded bedding.Cables up to 400sqmm conform to BS6346. 500sqmm cable conforms to IEC 60502-1.