Leave Your Message
Products Categories
Featured Products

BS H07V-K 450/750V Flexible Single Conductor PVC Insulated Hook-up Wire

H07V-K 450/750V Cable is flexible harmonized single-conductor PVC insulated hook-up wire. H07V-K single-core flex cable is named according to harmonized standard. In British, the H07V-K cables refer to 2491X. H07V-K cable/wire features flex copper conductor class 5 and PVC insulation with voltage 450/750V.

    Application

    H07V-K 450/750V Cable is widely used in the ground above or fixed in pipes or in similar closed systems. The cable is a good option to protected installation in lighting and control appliances for voltage up to 1000V in c.a. or up to 750 V in c.c. landward. Not allowed to be used in water.

    Technical Performance

    Operating voltage 450/750V 
    Test voltage 2000V(H05V-U)/2500V
    Dynamic bending radius 15 x Ø
    Static bending radius 15 x Ø
    Operating temperature -5°C to +70°C
    Static temperature -30°C to +90°C
    Temperature reached in short circuit +160°C
    Flame retardant IEC 60332.1
    Insulation resistance 10 MΩ x km

    Constructions

    Conductor: Class 5 flexible copper conductor as per BS EN 60228 (BS 6360)

    Insulation: PVC (Polyvinyl Chloride) insulation

    Color: yellow / green, red, yellow, blue, white, black, green, brown, orange, purple, gray or as per your requirements

    Specifications

    IEC 60227 , BS6004, UL1581, UL83

    Data Sheet

    BS 450/750V H07V-K Cable Specification
    Size Core No. X Conductor area Insulation thickness Overall Diameter Nominal copper weight Nominal cable weight (kg/km)
    (AWG) ( No. x mm2) (mm) (mm) (kg/Km)
    H05V-K
    20(16/32) 1 x 0.5 0,6 2.1 4.9 10
    18(24/32) 1 x 0.75 0,6 2.4 7.2 13
    17(32/32) 1 x 1 0,6 2.6 9.6 15
    H07V-K
    16(30/30) 1 x 1.5 0,7 3.1 14.4 20
    14(50/30) 1 x 2.5 0,8 3.6 24 31
    12(56/28) 1 x 4 0,8 4.3 38 48
    10(84/28) 1 x 6 0,8 4.9 58 69
    8(80/26) 1 x 10 1,0 6.4 96 121
    6(128/26) 1 x 16 1,0 8.1 154 211
    4(200/26) 1 x 25 1,2 9.8 240 303
    2 (280/26) 1 x 35 1,2 11.1 336 417
    1 (400/26) 1 x 50 1,4 13.1 480 539
    2/0 (356/24) 1 x 70 1,4 15.5 672 730
    3/0 (485/24) 1 x 95 1,6 17.2 912 900
    4/0 (614/24) 1 x 120 1,6 19.7 1152 1135
    300 MCM (765/24) 1 x 150 1,8 21.3 1440 1410
    350 MCM (944/24) 1 x 185 2,0 23.4 1776 1845
    500MCM(1225/24) 1 x 240 2,2 27.1 2304 2270

    H07V-K

    Normal size conductor diameter Average insulation thickness External diameter Max resistance at 20 Approx cable weigh
    coresxmm2 mm mm mm Ω/km kg/km
    1x1.5 1.5 0.7 3.4 13.3 20
    1x2.5 2 0.8 4.1 7.89 31
    1x4 2.5 0.8 4.8 4.95 45
    1x6 3 0.8 5.3 3.3 64
    1x10 4 1 6.8 1.91 110
    1x16 5 1 8.1 1.21 160
    1x25 6.2 1.2 10.2 0.78 250
    1x35 7.4 1.2 11.7 0.554 340
    1x50 8.9 1.4 13.9 0.386 480
    1x70 10.5 1.4 16 0.272 670
    1x95 12.2 1.6 18.2 0.206 870
    1x120 13.8 1.6 20.2 0.161 1100
    1x150 15.4 1.8 22.5 0.129 1370
    1x185 16.9 2 24.9 0.106 1680
    1x240 19.5 2.2 28.4 0.0801 2205