BS 6004 6241Y 6242Y 6243Y Cable PVC Insulated And Sheathed Flat Twin And Earth Wire

6241Y 6242Y 6243Y Cable PVC Insulated And PVC Sheathed Flat Twin And Earth Wire with bare circuit protective conductor CPC.

    Application

    6241Y 6242Y 6243Y Cable is suitable for fixed installation in dry or damp premises on walls, boards or trays, in channels or embedded in plaster. They should be laid in conduit or trunking where mechanical protection is required. Widely used in lighting and domestic buildings. These cables are particularly suited for installation as meter tails and are used for fixed installation in the condition of dry or damp occasion.

    These cables can be fixed with clip directly or by cable tray or embedded or in free air. They are not allowed to be laid underground.

    Technical Performance

    Rated Voltage (Uo/U) 300/500V
    Test voltage 2000 volts
    Minimum bending radius 4xOverall diameter
    Flexing temperature -15 ℃ to +70 ℃ 
    Short circuit temperature +160 oC
    Flame retardant IEC 60332.1
    Insulation resistance 10 MΩxkm

    Constructions

    Conductor: Annealed solid or stranded copper conductor as per IEC 60228, class 1 or class 2

    Insulation: Insulated with Cross linked compound type GP8 or EI 5 confirming to BS 7655-1.3/BS EN 50363-5

    CPC: Bare circuit protective conductor

    Sheath: Sheathed with Halogen free material Type LTS4 confirming to BS 7655-6.1

    Color: – Single core Brown or Blue

    – 2 core Brown and Blue or 2 x 1 & 2 x 1.5 cables, Brown and Brown

    – 3 core Brown, Black (Centre core), Grey

    Specifications

    BS 6004: 2012+A1:2020 standard for Electric cables. PVC insulated and PVC sheathed cables for voltages up to and including 300/500 V

    Data Sheet

    BS 6004 6241Y 6242Y 6243Y Cable Specifications
    AWG (No of Strands/Strand Diameter) No. of Cores x Nominal Cross Sectional Area Nominal thickness of insulation Nominal thickness of sheath Nominal overall dimensions Circuit protective conductor Nominal Weight
    lower limit upper limit
    No.x mm2 mm mm mm mm AWG kg/km
    6241Y
    17 1 × 1.0 0.6 0.9 4x5.1 5.2x6.4 17 45
    16 1 × 1.5 0.7 0.9 4.4x5.4 5.8x7.0 17 55
    6242Y
    17 2 × 1.0 0.6 0.9 4 × 7.2 4.7 × 8.6 17 68
    17(7/26) 2 × 1.0 0.7 0.9 4.2 × 7.8 5.1 × 9.4 17 73
    16 2 × 1.5 0.7 0.9 4.4x8.2 5.4x9.6 17 85
    16(7/24) 2 × 1.5 0.7 0.9 4.5x8.4 5.6x10 17 90
    14 2 × 2.5 0.8 1 5.2x9.8 6.2x11.5 16 120
    14(7/22) 2 × 2.5 0.8 1 5.2x9.8 6.6x12.0 16 125
    12(7/20) 2 × 4 0.8 1 5.6x10.5 7.2x13.0 16 175
    10(7/18) 2 × 6 0.8 1.1 6.4x12.5 8.0x15.0 14 240
    8(7/16) 2 × 10 1 1.2 7.8x15.5 9.6x19.0 12(7/20) 390
    6(7/14) 2 × 16 1 1.3 9.0x18.0 11.0x22.5 10(7/18) 560
    6243Y
    17 3 × 1.0 0.6 0.9 4x9.6 4.7x11.0 17 91
    16 3 × 1.5 0.7 0.9 4.4x10.5 5.4x12.5 17 115
    14 3 × 2.5 0.8 1 5.2x12.5 6.2x14.5 17 170
    12(7/20) 3 × 4 0.8 1.1 5.8x14.5 7.4x18.0 16 250
    10(7/18) 3 × 6 0.8 1.1 6.4x16.5 8.0x20.0 14 340
    8(7/16) 3 × 10 1 1.2 7.8x21.0 9.6x25.5 12(7/20) 540
    6(7/14) 3 × 16 1 1.3 9.0x24.5 11.0x29.5 10(7/18) 790
    6242Y
    Cross-sectional No. & diameter of wire Nominal earth core size (mm²) Overall diameter (mm) Reference weight (kg/km) Insulation Resistance (MΩ • km) 70 C Min
    Area (mm²)
    2 x 0.75 1/0.98 1 3.8 x 7.2 54 0.012
    2 x 1.0 1/1.13 1 4.1 x 7.8 65 0.011
    2 x 1.5 1/1.38 1 4.4 x 8.3 77 0.011
    2 x 2.5 1/1.78 1 5.2 x 9.8 109 0.01
    2 x 4.0 7/0.85 1.5 6.0 x 11.7 164 0.0077
    2 x 6.0 7/1.04 2.5 7.3 x 14.1 243 0.0065
    2 x 10 7/1.35 4 8.6 x 17.3 376 0.0065
    2 x 16 7/1.7 6 10.0 x 20.2 551 0.0052