01
BS 300/500V H05V-K Cable Harmonized PVC Single Core Flexible Wire
Application
H05V-K Cable is mainly used in the switch control, relay and instrumentation panels of power switch-gear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.Not allowed to be used in water.
Technical Performance
Operating voltage | 300/500V |
Test voltage | 2000V(H05V-U)/2500V |
Dynamic bending radius | 15 x Ø |
Static bending radius | 15 x Ø |
Operating temperature | -5°C to +70°C |
Static temperature | -30°C to +90°C |
Temperature reached in short circuit | +160°C |
Flame retardant | IEC 60332.1 |
Insulation resistance | 10 MΩ x km |
Constructions
Conductor: Multiple stranded flexible copper conductor (class 5),Comply with VDE-0295 Cl 5, IEC 60228 Cl-5
Insulation: PVC (Polyvinyl Chloride) type TI-1 according to BS7655 and HD 21.3S3:1995/A2:2008.
Color: yellow / green, red, yellow, blue, white, black, green, brown, orange, purple, gray or as per your requirements.
Specifications
IEC 60227 , BS6004, UL1581, UL83
Data Sheet
BS 300/500V H05V-K Cable Specification | |||||
Size | Core No. X Conductor area | Insulation thickness | Overall Diameter | Nominal copper weight | Nominal cable weight (kg/km) |
(AWG) | ( No. x mm2) | (mm) | (mm) | (kg/Km) | |
20(16/32) | 1 x 0.5 | 0,6 | 2.1 | 4.9 | 10 |
18(24/32) | 1 x 0.75 | 0,6 | 2.4 | 7.2 | 13 |
17(32/32) | 1 x 1 | 0,6 | 2.6 | 9.6 | 15 |
Normal size | conductor diameter | Average insulation thickness | External diameter | Max resistance at 20 | Approx cable weigh |
coresxmm2 | mm | mm | mm | Ω/km | kg/km |
1x0.5 | 0.9 | 0.6 | 2.5 | 39 | 9 |
1x0.75 | 1.1 | 0.6 | 2.7 | 26 | 11 |
1x1 | 1.3 | 0.6 | 2.8 | 19.5 | 14 |