ASTM Standard 25kV XLPE Insulated MV Middle Voltage Power Cable

25kV cable is suitable for use in wet and dry areas, conduits, ducts, trenches, trays, direct burial and where electrical performance is superior when installed closely with a grounded conductor complying with NEC Sections 311.36 and 250.4(A)(5) Properties are required. The cables are capable of continuous operation at conductor temperatures not exceeding 105°C in normal operation, 140°C in emergency overload conditions, and 250°C in short-circuit conditions. Cold bend rated to -35°C. ST1 (Low Smoke) is rated for sizes 1/0 and larger. The PVC sheath is made with SIM technology and has a coefficient of friction COF of 0.2. The cable can be installed in the conduit without lubrication. Rated for maximum sidewall pressure of 1000 lb/ft.

    Application

    25kV CU 133% TRXLPE Full Neutral LLDPE Primary used for primary underground distribution in conduit systems suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 25,000v or less, conductor temperatures not to exceed 90°C during normal operation.

    Construction

    Conductor: Class A or B Compressed concentric stranded aluminum alloy, Aluminium or copper conductor. Stranded conductors are water-blocked with conductor filling compound.Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TR-XLPE) as defined in ANSI/ICEA S-94-649 - 133% insulation level.Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.Metallic Shield: Solid bare copper wires helically applied and uniformly spaced.Water Block: Water-blocking agents applied over the insulation shield and around the neutral wires to resist longitudinal water penetration. Longitudinal water penetration shall be tested in accordance with the latest edition of ICEA T-34-664 except that the minimum requirement is 15 psig for 1 hour.Jacket: Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes.

    Specifications

    ASTM B3 Standard Specification for Soft or Annealed Copper Wire.

    ASTM B8 Concentric-Lay-Stranded Copper Conductors.

    ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV.

    AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV.

    Data Sheet

    25kV CU 133% TRXLPE Full Neutral LLDPE Primary UD

    No. of Conductors Size (mm2) No. of Strands Insulation Thickness (mm) Nom. OD (mm) Nominal Total Weight (kgs/km)
    1 2 AWG 7 6.6 29.24 811
    1 1 AWG 19 6.6 30.23 995
    1 1/0 AWG 19 6.6 30.99 1105
    1 2/0 AWG 1 6.6 31.32 998
    1 4/0 AWG 19 6.6 35.21 1328
    1 350 KCMIL 37 6.6 39.6 1823
    1 500 KCMIL 37 6.6 45.07 2436
    1 750 KCMIL 61 6.6 49.88 3235
    1 1000 KCMIL 61 6.6 55.49 4137