AS/NZS standard 3.8/6.6kV XLPE Insulated MV Medium Voltage Power Cable

Power distribution or secondary transmission network cables are commonly used as the main power supply for commercial, industrial, and urban residential networks. Suitable for high fault level systems, with a current rating of up to 10kA/1sec. Structure with higher fault current ratings can be provided upon request.

    Application

    Power distribution or secondary transmission network cables are commonly used as the main power supply for commercial, industrial, and urban residential networks. Suitable for high fault level systems, with a current rating of up to 10kA/1sec. Structure with higher fault current ratings can be provided upon request.

    Temperature range

    Install min temperature

    0°C

    Working max temperature

    +90°C

    Working min temperature

    -25 °C

    Minimum bending radius

    Install cables

    12D (PVC)  15D (HDPE)

    During installation

    18D (PVC) 25D (HDPE)

    Resistance to Chemical exposure

    Accidental

    Mechanical impact

    Light (PVC only)  Heavy (HDPE)

    Water exposure

    XLPE – Spray  EPR – Immersion/Temporary coverage

    Solar radiation and weather exposure

    Can be direct exposure.

    Construction

    Manufacturing and type testing in accordance with AS/NZS 1429.1, IEC: 60502-2 or equivalent

    Structure:  1 core, 3 core, 3×1 core Triplex

    Conductor: Cu or AL, Stranded Circular, twisted Compact Circular, Milliken Segmented

    Insulate: XLPE or TR-XLPE or EPR

    Metallic screen or sheath: Copper Wire Screen (CWS), Copper Tape Screen (CTS), Lead alloy sheath (LAS), Corrugated Aluminium sheath (CAS), Corrugated Copper sheath (CCU), Corrugated Stainless Steel (CSS), Aluminium poly laminated (APL), Copper Poly Laminated (CPL), Aldrey wire screen (AWS)

    Armour: Aluminium Wire Armoured (AWA), Steel Wire Armoured (SWA), Stainless Steel Wire Armoured (SSWA)

    Termite Protection: Polyamide Nylon Jacket, Double brass tape (DBT), Cypermethrin

    Black 5V-90 polyvinyl chloride (PVC) : standard

    Orange 5V-90 PVC inner layer with black high density

    Polyethylene (HDPE) outer : alternative

    Low smoke zero halogen (LSOH) : alternative

    Data Sheet

    3.8/6.6kV-Power cable

    Cores x Nominal Area Conductor diameter (Approx.) Nominal Insulation Thickness Approx. CWS area on each core Nominal Thickness of PVC Sheath Overall Cable diameter (+/- 3.0) Short Circuit rating of Conductor/ CWS Cable Weight (Approx.) Max. Conductor DC Resistance at 20 °C
    No. X mm2 mm mm mm2 mm mm kA for 1sec kg/km (Ohms/km)
    1Cx 35 7.0 2.5 24 1.8 21.8 5 / 3 982 0.524
    1Cx 50 8.1 2.5 24 1.8 22.9 7.2 / 3 1140 0.387
    1Cx 70 9.7 2.5 79 1.8 26.9 10 / 10 1886 0.268
    1Cx 95 11.4 2.5 79 1.8 28.2 13.6 / 10 2145 0.193
    1Cx 120 12.8 2.5 79 1.8 29.6 17.2 / 10 2397 0.153
    1Cx 150 14.2 2.5 79 1.8 31.0 21.5 / 10 2701 0.124
    1Cx 185 16.1 2.5 79 1.9 32.5 26.5 / 10 3045 0.0991
    1Cx 240 18.5 2.6 79 2.0 35.1 34.3 / 10 3611 0.0754
    1Cx 300 20.6 2.8 79 2.1 37.6 42.9 / 10 4246 0.0601
    1Cx 400 23.6 3.0 79 2.2 41.2 57.2 / 10 5246 0.0470
    1Cx 500 26.6 3.2 79 2.3 44.8 71.5 / 10 6254 0.0366
    1Cx 630 30.2 3.2 79 2.4 48.6 90.1 / 10 7521 0.0283