Leave Your Message
Products Categories
Featured Products

60227 IEC 07 BV Solid Indoor Copper Building Wire Single Core PVC Insulated No Sheath 90C

Single core 90℃ solid conductor unsheathed cable for internal wiring.

    Application

    60227 IEC 07 BV Solid Indoor Copper Building Wire is suitable for fixed wiring and installation, indoor and outdoor, in surface mounted or embedded conduits, or similar closed systems, but they are not suitable for mobile equipment.

    Technical Performance

    Rated Voltage (Uo/U) 300/500V
    Conductor temperature Maximum conductor temperature in normal use: 90ºC
    Installation temperature Ambient temperature under installation shall not be below 0ºC
    Minimum bending radius
    The bending radius of cable (D-Diameter of cable) 
    D≤25mm------------------≥4D
    D>25mm------------------≥6D

    Constructions

    Conductor: Number of conductors:1

    The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2

    – class 1 for solid conductors

    – class 2 for stranded conductors

    Insulation: PVC(Polyvinyl Chloride) Type PVC/C according to IEC

    Color: yellow / green, blue, black, red, white, brown, orange, purple, gray etc

    Specifications

    60227 IEC 07 Standard

    Data Sheet

    60227 IEC 07 Single Core PVC Insulated No Sheath 90C RV Solid Building Wire
    Nominal cross-sectional area of conductor mm2 Class of conductor Nominal insulation thickness mm Mean overall diameter Max mm Approx, weight of cable kg/km Max. D. C. resistance of copper conductor (20℃) Ω/km Min. insulation resistance (90℃ Ω/km)
    Plain Metal-coated
    0.5 1 0.6 2.3 8 36 36.7 0.015
    0.8 1 0.6 2.5 10 24.5 24.8 0.013
    1 1 0.6 2.7 13 18.1 18.2 0.012
    1.5 1 0.7 3.2 19 12.1 12.2 0.011
    2.5 1 0.8 3.9 30 7.41 7.6 0.009