01
60227 IEC 07 BV Solid Indoor Copper Building Wire Single Core PVC Insulated No Sheath 90C
Application
60227 IEC 07 BV Solid Indoor Copper Building Wire is suitable for fixed wiring and installation, indoor and outdoor, in surface mounted or embedded conduits, or similar closed systems, but they are not suitable for mobile equipment.
Technical Performance
Rated Voltage (Uo/U) | 300/500V |
Conductor temperature | Maximum conductor temperature in normal use: 90ºC |
Installation temperature | Ambient temperature under installation shall not be below 0ºC |
Minimum bending radius | |
The bending radius of cable | (D-Diameter of cable) |
D≤25mm------------------≥4D | |
D>25mm------------------≥6D |
Constructions
Conductor: Number of conductors:1
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2
– class 1 for solid conductors
– class 2 for stranded conductors
Insulation: PVC(Polyvinyl Chloride) Type PVC/C according to IEC
Color: yellow / green, blue, black, red, white, brown, orange, purple, gray etc
Specifications
60227 IEC 07 Standard
Data Sheet
60227 IEC 07 Single Core PVC Insulated No Sheath 90C RV Solid Building Wire | |||||||
Nominal cross-sectional area of conductor mm2 | Class of conductor | Nominal insulation thickness mm | Mean overall diameter Max mm | Approx, weight of cable kg/km | Max. D. C. resistance of copper conductor (20℃) Ω/km | Min. insulation resistance (90℃ Ω/km) | |
Plain | Metal-coated | ||||||
0.5 | 1 | 0.6 | 2.3 | 8 | 36 | 36.7 | 0.015 |
0.8 | 1 | 0.6 | 2.5 | 10 | 24.5 | 24.8 | 0.013 |
1 | 1 | 0.6 | 2.7 | 13 | 18.1 | 18.2 | 0.012 |
1.5 | 1 | 0.7 | 3.2 | 19 | 12.1 | 12.2 | 0.011 |
2.5 | 1 | 0.8 | 3.9 | 30 | 7.41 | 7.6 | 0.009 |